Impressum | AGB | KontaktDE | EN

Technical data

Rated voltage up to

12

kV

Input voltage

2,3-11

kV

Output voltage

2,3-11

kV

Starting voltage range

0-11

kV

Rated starting time

5-90

sec

Rated starting current up to

520

A

Rated by-pass current up to

2500

A

Rated short time current up to

40

kA

Rated peak withstand current up to

100

kA

Rated starting power up to

10.000

kVA

full load

Motor starting up to

20.000

kW

partial load

Operating frequency

0-65

Hz

Output frequency resolution

0,01

Hz

Control

Totally digital with signal processor,

PLC and 5" color HMI

Control mode

V/F or vector control, open & closed

loop with encorder

Cooling method

NA / FA

air cooling

Heat dissipation sample 

< 0,15

kWh

by-pass closed
(without stand still heater)

Additional heat dissipation sample

0,11-2,1

kWh

Enclosure protection class

IP 3X

acc. to IEC 61800

Painting of doors

RAL 7035 (light grey)

Steel sheet panel external

covers powder coated, frame galvanized

Ambient requirements

Indoor, normal air, refer to 4.2.6.2.2 of IEC 61800-5-1 pollution degree 2

Altitude above sea level

≤ 1000

m

Rated ambient temperature

40

 

Ambient temperature

0 ~ + 55

- 40 ~ + 70

 

 

de-rated operating
storage

Designed under consideration of

IEC 61800-5-1; IEEE 519-2000

Height / Depth
Width

2400/1300 
3250-7800

mm
mm


complete with MV contactors & control



Explanations:
Some illustrations on this websites are typical or show options and might vary from standard and real design. Higher and other values can be offered on request.

809